The function of wiring safety codes is to give
technical, performance and material standards that would allow proper use of
the electrical energy. Materials required for wiring a building depend on
factors like rating of the circuit, type of occupancy of the building, type of
electrical system, national and local regulations and conditions in which the
wiring must operate. The design and planning of an electrical wiring
installation involve consideration of all prevailing conditions such as the
type of supply, envisaged load, earthing arrangements, safety aspects and
energy conservation. It is essential that adequate provision is made for all
services such as lighting, power requirement for A/C, fridge and kitchen
heating. Proper planning will prevent the householder from relying on the use
of long flexible cables and multi-plug adopters which are dangerous and not
recommended.
Estimation of load
requirement
All conductors and switches and other accessories should be having
a rating such that they are not exceeded under any circumstance of use. This
may be calculated knowing the rating(W) of the lights fans and equipments
connected. The size of the conductor of the circuit should be chosen so as to
permit only minimum voltage drop form the inlet to any point in the
installation. In each circuit or sub-circuit the fuse shall be such as to match
the cable rating to ensure desired protection.
Installation
In the case of concealed wiring, installation should begin
immediately on completion of the main structural work and before finishing
works such as plastering . In the case of surface wiring, it can be carried out
after plastering . Generally, installation should not start before the building
is reasonably weatherproof. However, where electrical wiring is to be concealed
within the structure as in a RCC building, the necessary conduits or ducts
shall be positioned firmly and tied to the reinforcement before concreting.
When shutters are removed after concreting, the conduit ends shall be sealed by
caps to protect them from getting blocked. All conduit openings and junction
box openings should be protected against entry of muck or mortar during
construction.
Conductors for all internal wiring may be of copper. The conductor
for final sub-circuit for fan and light wiring should be not less than 1.5 mm2
of copper and for power cable not less than 4.0 mm2 of copper. In existing
buildings it is advisable to replace wiring which is more than 30 years old as
the insulation in it would have deteriorated. This will be in a state to cause
failure leading to short circuit on the slightest of either mechanical or
electrical disturbances.
Accidental shock
Earthing is required to by-pass the over-rated current caused due
to fluctuation in circuit parameters such as phase frequency and line voltage
etc., to save human life and electrical assets from short circuits.
Fuse is a conditional switch having fuse wire of low melting point
required to save the electrical network in case of overloads and short
circuits. Short circuit occurs due to accidental contact of phase with another
phase or phase with neutral or phase with earth wire.
Use of RCCB/ ELCB (Residual current circuit breaker/ Earth Leakage
circuit breaker) prevents the accidental shocks and also keeps a check on the
earthing system of the house. In case of leakage of very small current in
milli-amperes would trip the circuit and prevent the mishap.
Concealed wiring
Concealed wiring is safe for the building as long as it is
properly placed and joints are properly covered. There should be tap holes for
checking the wiring at suitable intervals. The wiring should not be too close
to the slab and also from the wet areas in the building. The wiring should not
be exposed to external cracks in the walls. While concealing and embedding
inserts into a structural member care should be exercised to see that the
member is not made weaker. A 6 inch switch box cannot be inserted into a 9 inch
column.
Thus the benefits of greater personal and equipment safety,
reliability, current load capacity, discharge path for short circuits, fault
current/surge protection, stable earth values, low resistance, longer life, and
low cost maintenance can all be achieved by proper planning and installation of
electric wiring.
Safety instructions
•Always buy electrical items that carry the ISI mark
•Identify locations for switchboards in advance so that they will
not be an obstruction when the room is being decorated
•Proper earthing should be done for the entire house
•Each power board should have a separate fuse
•Registered electrical contractors should be engaged to carry out
the electrical work
•Consumption of electricity should be need based. Try to save
electricity as much as possible
•The entire network should be designed to avoid unnecessary or
excess power loss during transmission
https://kep-power-testing-blog.blogspot.com/2016/11/manufacturing-electrical-cable.html?showComment=1635404791541
ReplyDeleteGreat! your article is very nice and interesting. if your looking for best Commercial Electrical Contractors services. so please visit our site.
ReplyDeleteFully screened, drug tested, and background checked for your peace of mind Neat, clean and uniformed for safety and security Friendly, helpful, and reliable. We don’t hire anyone we wouldn’t hire to work inside of our own homes. Knowledgeable, experienced and skilledelectrical services
ReplyDeleteThis is the kind of blog I was looking from a long time. CZ Electric, the best electrical contractors, offers commercial, industrial electrical service in Orange County, Anaheim. Call Today!
ReplyDeletecommercial electric company Fullerton Irvine
Keep sharing such informative blogs. I was looking for electricians provides commercial, industrial electrical services, keep sharing such posts.
ReplyDeletehome electrical contractor Brea